Type 2 HE75 Baffle Filter
Type 2 HE75 High Performance 75% Grease Efficiency Baffle Filter
496(H)x496(W)x45(D)mm
For use in commercial kitchens and ventilation to extract grease laden air and act as a fire barrier. LONGAR® Type 2 HE75 is a positive flame barrier having been tested to European DIN Standard 18869-5 & American 1046 & ASTM2519.
The LONGAR® TYPE 2 HE75 is developed for customers who wish to extract more grease from the air stream, following prolonged R&D we have designed a baffle filter with a micro screen on the exit to increase grease extraction.
The result of this is a retrofit baffle filter that removes 75% of the grease at 8 microns. Tested to ASTM2519 this product significantly reduces duct cleaning, saving customers expenditure on ongoing cleaning costs.
Conventional baffle filters extract grease in the region of 20 to 35% efficiency at 8 microns depending on the product design, the HE75 offers over twice the extraction rate.
SPECIFICATIONS
Construction / Material Specification:
As standard all baffles are manufactured with Stainless Steel 430 polished finish. Maximum operating temperature 400C or 750F.Packaging:
All units are packaged in double wall boxes with separators for standard sizes, glued closed for protection whilst in transit against contamination.Filter Classification:
- Filter Class G2
- UL Class 2
Tested To:
- DIN 18869-5
- UL 1046
- ASTM 2519
Manufactured To:
- DW172
- ISO9001
FEATURES & APPLICATIONS
Features:
- High Performance Baffle Filter 75% Grease efficiency at 8 micron
- 100% Flame barrier protection to DIN 18869-5
- Cutsafe safety edges
- Fully welded construction – all stainless steel construction
- Meets insurance requirements
- Meets HVCA DW172 requirements
- Folding handles and drain holes as standard
- Robust baffle filter construction – built to last
- Tested & certified to European standard DIN 18869-5
- Tested to American standard UL1046
- Tested & certified to ASTM 2519
Applications:
- Commercial kitchens
- Water mist separation
- Spark arrestors
- Sand filtration
- Grease filtration
FIT INSTRUCTIONS & MAINTENANCE
Fitting Instructions:
- Fit products, handles in direction of air in
- Product vertical in air stream
Handling:- Handle with care when unpacking
- Store in dry and frost protected place
Maintenance:
- All maintenance should be carried out in accordance with the planned maintenance set by installation contractor
- When handling any components suitable PPE should be used - gloves, eye protection and access equipment
- Filters should be cleaned by a trained operative either daily for heavy use or weekly for light use
- For more exact guide to cleaning you should contact a cleaning specialist